Advanced Earth Resistance Tester MS2308

♦Test voltage have 20V/48V Provide choice.      
♦2 pole resistance measurement.      
♦3 pole & 4 pole earth resistance measurement.      
♦4 pole soil resistivity testing.      
♦Current Clamp selection method is used to measuring earth resistance without breaking grounding connection.  
♦Double clamp without auxiliary electrode is used to fast measuring grounding resistance.  
♦Auto and manual control the test frequency. Have 94 Hz,105Hz,111Hz,128Hz for frequency provide choice.
♦Automatic frequency control (AFC) is automatically identified interference frequency and then selected the proper measurement frequency, so that reduced the affect of interference voltage.      
♦Automatically measuring the interference voltage and the leakage current. The limited value will be alarmed.  
♦ Auto power off      
♦Clock display      
♦Double battery power supply and low battery indication      
♦Data storage: Can memorize u p to 100 measuring values, and uploading to PC by USB2.0 interface. 

Specification
  Function MS2308 MS2307 MS2306
3 Pole & 4Pole Voltage: AC20/48V
Frequency: 94Hz, 105Hz,111Hz,128Hz,AFC,
Resistance±(5%rdg + 5dgt)


0.02Ω-300KΩ


0.1Ω-30KΩ

94Hz & 128Hz
0.1Ω-20KΩ
3 Pole & 4 Pole with current clamp Voltage: AC20/48V
Frequency: 94Hz, 105Hz,111Hz,128Hz,AFC,
Resistance±(5%rdg + 5dgt)


0.02Ω-19.99KΩ


0.1Ω-10KΩ
 
Double clamp Voltage: AC48V
Frequency: 94Hz, 105Hz,111Hz,128Hz,AFC,
Resistance±(10%rdg + 5dgt)


0.02Ω-140Ω


0.1Ω-140Ω
 
R~2 Pole Voltage: AC20V
Frequency: 94Hz, 105Hz,111Hz,128Hz,AFC,
Resistance±(5%rdg + 5dgt)


0.02Ω-300kΩ


0.1Ω-30KΩ

94Hz & 128Hz
0.1Ω-20KΩ
R-2/4 Pole Voltage:DC20V
Resistance:±(5%rdg + 5dgt)

0.02Ω-3kΩ
   
Rk Voltage: AC20/48V/DC20V
Frequency: 94Hz, 105Hz,111Hz,128Hz,AFC,
Resistance±(5%rdg + 5dgt)


0.02Ω-29.99Ω


0.1Ω-29.99Ω

94Hz & 128Hz
0.1Ω-29.99Ω
Test Short Current   250mA 100mA 100mA
Soil Resistivity Voltage: AC20V/48V
Frequency:94Hz, 105Hz, 111Hz,128Hz,AFC
Range:1Ωm~9999kΩm±(5%rdg + 5dgt)





94Hz&128Hz
Disturb Voltage
Current and Frequency
Voltage:±1V~±50VDC/AC±5%rdg+5dgt
Frequency:16Hz~400Hz ±1%rdg.+2dgt
Current:20mA~2A: ±5%rdg+5dgt.






 
USB2.0
Data Storage
 
Manually store 100 groups


 
Power supply LR14X6;Voltage:9V
Recharge Battery: NI~MH recharge Battery,7.2V
Charger: Input voltage: 100V~240V Frequency: 50Hz~60Hz Output voltage: 12VDC 3A
Display LCD display, with Back light. Max 9999
Dimension 230(w)-125(H)-284(L)mm
Weight  Approx.2.5Kg Approx.2.5Kg Approx.2Kg

Send your message to this supplier


Related Articles from the Supplier

Related Articles from China Manufacturers

Related Products Mentioned in the Article

Mastech Meters & Testers Co., Ltd.

Mastech Meters & Testers Co., Ltd.


Supplier Website

Source: https://www.meterstesters.com/products/earth-resistance-testers/advanced-earth-resistance-tester-ms2308.html